HDPE Pipes
HDPE Pipes and fittings shall be to DIN 8074/8075 or AWWA C906-99. Pipe. The ends of
each pipe shall be plain and suitable for heat fusion. Pipe and fittings shall be class 10 or
16 kg/cm2. Materials used shall have a standard PE code designation 3408 and a minimum
hydrostatic design basis of 1600 psi according to AWWA C906 Table 1. Manufacturers
shall provide certification that stress regression testing has been performed on the pipe products. Materials shall also meet elevated temperature requirements as given in Table 2
AWWA C906. HDPE Fittings shall be to AWWA C906, extruded or injection moulded
suitable for class of pipe required. Joints for HDPE pipes and fittings shall be by heat fusion and in strict accordance with pipe manufactures recommendations. Joints shall have
a tensile strength equal to that of the pipe. Fusion temperature, interface pressure, alignment and cooling time, shall be according to manufactures recommendations. Tests on HDPE Compounds: HDPE compounds in pipes and fittings shall contain no
ingredients in an amount that has been demonstrated to migrate into water in quantities
considered to be toxic. HDPE compounds shall be tested and certified suitable for potable
water by the National Sanitation Foundation (NSF) Testing Laboratory – USA, or the
Canadian Standard Association (CSA) Testing Laboratory, or other accredited testing agency. Tests shall be made in accordance with requirements no less restrictive than those
in the NSF Standard No. 14 (1976), Sections 3 and 4. The seal and mark of the testing laboratory shall be included on pipes and fittings.
uPVC PIPE AND FITTINGS
uPVC pipes shall conform to AWWA C900, Class 200, with bell end with gasket, and with
spigot end. The pipes shall conform to the following specific requirements: • Comply with UL 1285 for fire-service mains.
• PVC Fabricated Fittings: AWWA C900, Class 200, with bell-and-spigot or
doublebell
ends. Include elastomeric gasket in each bell.
• PVC Molded Fittings: AWWA C907, Class 150, with bell-and-spigot or double-bell ends. Include elastomeric gasket in each bell.
----------------------------精品word文档 值得下载 值得拥有----------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------
----------------------------精品word文档 值得下载 值得拥有----------------------------------------------
• Push-on-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.
• Gaskets: AWWA C111, rubber.
• Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard
pattern or AWWA C153, ductile-iron compact pattern. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.
----------------------------精品word文档 值得下载 值得拥有----------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------
本文档为【pe管英文规范】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。