Information Center UPS
technique
art
build
Discussion
book
VER100301
Changsha Taihe Yingjie System Integration Engineering Co Ltd
Two O O April
Catalog
I. system design and planning 3
1.1 system overview 3
1.2 system design according to 3
1.3 system design principles and system features 4
Two, UPS design 5
2.1 overview 5
2.2 UPS power distribution system 5
2.3 Emerson Adapt modular UPS system 6
2.4 battery system 11
System design plan
1.1 system overview
With the wide application of electronic computer in national defense, scientific research, production automation, management and other fields, nearly 20 years in our country such as bamboo shoots after a spring rain like built a lot of big, medium and small scale computer room, to ensure reliable computer for the computer to seek and build a suitable working environment, give full play to its design the performance, extend the service life of the machine and ensure that staff pay attention to the physical and mental health problems more and more construction, and become the pursuit of the goal.
Emerson network energy has the industry's most complete network of energy products lines, and its network of energy, all proprietary equipment for its own brand. Emerson network energy use their strong technological advantages, to provide integrated end-to-end solutions for customers, so as to reduce the overall cost of selection, procurement, project management of customers, greatly improve the construction speed and shorten the construction period, to speed up the room operation,
unified and reduced customer maintenance work interface, which helps customers focus on core business, improve the core competitiveness of our customers.
1.2 system design basis
The project will be designed and managed in accordance with national standards and industry standards. The referenced documents and standards include:
1. construction materials provided by the owner
2. construction site conditions and survey data
3. relevant national standards and regulatory documents:
* GB 50174-2008 code for design of electronic information system room
* GB 50462-2008 code for construction and acceptance of electronic information system room
* GB 50019-2003 code for design of heating ventilation and air conditioning
* GB 50243-2002 code for acceptance of construction quality of ventilation and air conditioning works
* GB 50311-2007 specification for integrated wiring system engineering design
* GB 50312-2007 code for acceptance of generic cabling system works
* GB/T 50314-2006, intelligent building design standards
* JGJ 16-2008 code for electrical design of civil buildings
* GB 50052-95 code for design of power supply and distribution systems
* GB 50303-2002 code for construction quality acceptance of building electrical engineering
* YD5040-2005 code for design of installation of communication power equipment
* YD5098-2005 code for design of lightning protection and earthing works of Communication Bureau (station)
* GB50057-2000 code for lightning protection design of buildings
* GB50343-2004 technical specification for lightning protection of building electronic information system
* GB 50370-2005 code for design of gas fire extinguishing systems
1.3 system design principles and system features
This system integrates AC uninterrupted power supply and
distribution system as a whole solution.
* versatility
The design of this system conforms to the national design standard;
* reliability
The equipment has good electromagnetic compatibility and electrical isolation performance, and does not affect the normal operation of other equipment;
The integrated power supply can be designed as a whole to ensure uninterrupted power supply of the main equipment;
* stability
All the products have been tested by the major telecom operators and data networks in the world for a long time. They have the leading technology, leading manufacturing and leading brands in the industry;
* security
Fu Hegao class immunity international standard, safe and reliable work;
* maintainability
The main equipment adopts modular structure design, which is
convenient for troubleshooting;
* extensibility
In the system design, full consideration is given to the late expansion of users, and a reasonable redundant design has been made;
* intelligent design
The main equipment, power monitoring system UPS adopts intelligent design, intelligent interface board does not need to buy;
* economy
The overall design of the system can reasonably design equipment capacity and reduce equipment costs. At the same time, the power integration solution also reduces the additional cost of equipment, and brings a one-stop service to equipment maintenance in the later stage;
Two, UPS design
2.1 overview
According to the technical requirements of the information center room, provide an uninterrupted communication system (UPS) product program.
2.2 UPS power distribution system
2.2.1 general description
* the power supply for the central room of the project adopts three-phase five wire system.
* the power supply for power equipment in the room is three-phase, five wire system and single-phase three wire system. Room air conditioning, new exhaust system, normal lighting, temporary repair socket, general office equipment, etc., are powered by municipal power. The equipment in the engine room, regional information equipment, emergency lighting, fire protection and security are all powered by UPS.
* strong and weak electrical systems are arranged separately and rationally designed. In the power room, the reasonable design, the total input, the power distribution cabinet, the city electricity output power distribution cabinet, the UPS output power distribution cabinet.
* the UPS system uses the Emerson Adapt series 10KVA UPS system as the main part of the uninterrupted power supply system, and the system backup time is designed according to the system full load delay time of 2 hours.
We this division centralized nearby power supply scheme, the first Rack frame design Emerson Rui style using Adapt system, the system can be directly installed in the equipment room cabinet near the column, greatly shorten the distance distribution system and load cabinet, cable laying and save expenses, further reduce power consumption, to achieve the
purpose of energy saving optimization; secondly provide the structure of the system more flexible, fully realized on-demand scalability without the need to invest a lot of infrastructure investment in advance, to protect the interests of users the maximum degree; again to routine maintenance and future expansion provides great convenience, reduce the difficulty of the work room management departments, improve work efficiency. All of the above advantages ensure the reliability and economy of the power supply and distribution system in the engine room.
2.3 Emerson Adapt modular UPS system
Feasibility analysis of 2.3.1 modular UPS system scheme
Because of its high reliability, easy expansion, easy installation and maintenance, energy saving and environmental protection, modular UPS system has become the future development trend of UPS, and we have adopted this kind of UPS system in this project.
* investment while developing
Modular UPS,
With a strong capacity to expand, you can achieve the edge of the development of investment on demand expansion requirements. According to our understanding, the user is not much use of existing equipment, modular UPS, without changing the existing room structure, can easily achieve expansion, ensure the reliability of the power supply system of the future.
* higher reliability
N+X is currently the most reliable power supply structure, N represents the total load required at least UPS number, X is representative of the redundant UPS number, which is the system can bear the fault UPS number, when X is larger, the reliability of the system will be higher. For example, one client has a total load of 32KVA, and a modular UPS is used as a N+1 redundancy design. The N is 2, the X is 1, and the redundancy level is 99.999%. You can also choose to do N+2 redundancy design, and its availability level is 99.99999%, so that users can improve the redundancy level according to the importance of the load.
* green energy saving
Using modular UPS, the power of UPS can be configured according to the actual situation of the existing load, so as to ensure the ideal matching of UPS and load, and achieve the best energy-saving effect.
Generally speaking, UPS is the most efficient under full load, but the lighter the load, the lower the efficiency. The two traditional UPS and UPS machine, the maximum load of up to 50%, according to statistics in most cases is not more than 40%, the load conditions of UPS efficiency are generally not more than 82%; if the use of modular UPS, such as 2+1 redundancy mode, the maximum load can reach 67%, the efficiency can be as high as 90% so, in terms of system efficiency, energy consumption, equipment utilization rate, investment protection and other aspects are the best. This design concept in environmental protection and energy saving is a good response to the current
state vigorously promote energy-saving emission reduction policy.
* modular UPS for easy handling, transportation and installation
Cabinet type traditional UPS as a whole, a single frame is relatively heavy, such as the capacity of the weight of 100KVA is about 1000kg, the size of more than 2m3, packaging, transportation, loading and unloading, the room door or aisle is small, lift truck is not enough, the floor plate can not support problems.
And the use of modular UPS, then the above problems will be resolved blade: 2 ~ 4 manpower that can fix the rack, 1~2 people can fix the module installation.
Traditional high-power UPS structure limits the use of vertical packaging and vertical transport, greatly limiting the choice of transport vehicles. And modular UPS system, because the module can be separately packaged, the rack can be horizontal packaging and transportation.
2.3.2 Emerson Adapt modular UPS system composition
* program: stand-alone system
order
Number
Device name type
Number
Remarks
One
Adapt 10KVA UPS
(UHA1R-0100L)
1 Taiwan
UPS module; output power factor 0.9; standard 19 inch rack type;
height 3U; weight 35Kg; full load input power factor 0.99; rack
type L guide rail
Two
12V100AH lead acid valve controlled battery
The 32 section
HUMBIRD (hummingbird); supports 9KW load for 2 hours delay
Three
16 section cabinet
2
Custom battery cabinet
2.3.3 Emerson Adapt series UPS system introduction
* applicable object
Server, storage, network equipment, ATM, VoIP, communication equipment, automation equipment, precision instrument, medical diagnosis equipment and other input voltage precision requirements of higher equipment.
* applicable circumstances
Small and medium-sized data / communication room, network, business hall, laboratory, instrument room, control room, office environment, billing center, precision control room, process control center, etc..
* Adapt series UPS features
* Adapt series UPS product positioning?
* applicable to server, computer room and other areas, protect servers, network communications and other key equipment
* fully match the overall program of Emerson Yi Rui TM engine room
* black body design highlights the harmony with the server and cabinet
* provide abundant rack options to facilitate the integration of power distribution / monitoring functions within the rack;
* how does the Adapt series UPS ensure the high reliability of power supply?
* double conversion online design, city power down without interruption
* supports N+X redundancy to achieve substantial improvements in system reliability
* DSP full digital control, high output voltage regulator accuracy
* using the latest IGBT devices to achieve input ultra wide range of anti grid fluctuations
* input standard anti surge circuit to achieve excellent anti grid surge capability
* how does Adapt series UPS bring about green environmental protection?
* the efficiency of the whole machine is as high as 92% or more, and the energy saving efficiency is obvious. (the 20KVA model selected in this project is up to 94%)
* the input power factor is as high as 0.99, and the utilization of electric energy is high
* satisfy EU RoHS directive, material / process free from toxic substances
* adjustable speed intelligent fan, automatic adjustment of fan speed, effective energy saving
* providing ECO operating mode with an efficiency of up to 98% and significant energy saving
* Adapt series UPS how to save money for you?
* up to 0.9 output power factor, carrying capacity boost 20-30%, matching the latest server's electrical characteristics
* high efficiency, low power consumption and low running cost
* the power density is high, the whole machine 2-3U, occupies the frame space to be small, saves the rack quantity (this project selected 20KVA model height is 3U)
* how convenient is the Adapt series UPS maintenance?
* full range of compatible rack / tower mounting methods
* super size LCD and LED show that the running data / system status / history is clear at a glance
* operation display panel rotation design, with different installation methods, free adjustment angle, convenient and intuitive
* how does the Adapt series UPS improve program availability?
* compatible with three single / single (5/10K), three single / 33 (16/20K) multiple applications
* support the parallel operation of the flexible cord (maximum 4 units, 3+1/2+2/4+0 optional), and without the need for parallel insertion, the system capacity is expanded at will
* easy extension of backup time by cascading battery modules
* how does the Adapt series UPS meet all monitoring needs?
* provide USB single monitor port
* provide SIC network adapter card which can collect environment quantity, and support server automatic security shutdown function
* background software compatible with a variety of operating systems (Windows/Linux/HP-UX/Sun, Solaris/IBM, AIX, etc.), compatible with Emerson computer monitoring platform SiteMonitor, support Web monitoring
* providing Mib libraries to facilitate access to all types of NMS network management systems
* how does the Adapt series UPS protect and prolong battery life?
* ultra wide input voltage / frequency range,
Effectively reduce the battery discharge probability and prolong the life
* temperature compensation function to reduce the effect of ambient temperature on battery life
* super charge capacity, effectively shorten the battery recharge time
* the number of battery packs is flexible to facilitate battery 16/20K
* support for common battery pack (16/20K), saving battery investment
* parameter characteristics
Adapt model
UHA1R-0100L
input parameter
Rectifier type
IGBT rectifier
Rated voltage
220/380Vac single phase three wire / three-phase four wire
Input voltage range
Single-phase 120Vac~288Vac
Input frequency range
45Hz~55Hz
Input power factor
Single phase = 0.99/, three-phase = 0.95
Battery
Battery type
Maintenance free battery for lead acid
Charging capacity
Mark the machine back to 90%<6h
Battery module type
U16-07C1
Battery module specification
430W * 660D * 88H (height inside frame 2U), 50KG
Output parameter
Rated power
10KVA/9KW
Rated voltage
Single-phase 220Vac
Voltage stability
3%
Frequency stability
0.25%
Distortion rate of output voltage waveform
<3% linear load, <5% nonlinear load
Maximum peak factor of load
3:1 (to meet IEC 62040-3)
Step load capacity
100%
Output mode
terminal
Overload capacity (% rated load)
105%~125% 5min; 125%~150% 1min; >150% 500ms
System parameters and standards
Transform type
Double transformation Online
Can the machine be combined?
Support the largest 4 units, and can set the 4+0, 3+1, 2+2 mode
Installation method
Rack / tower compatible
Overall efficiency
> 92.5%
Switching time
0 ms
Noise
<55 dB
language
Chinese and English
Do you have a LCD display?
Yes (optional)
Safety
IEC/EN 62040-1-1
electromagnetic compatibility
IEC/EN 62040-2; IEC/EN61000-3-11; IEC/EN 61000-3-12; YD/T
1095-2008
Surge protection
IEC/EN 62040-2
Protection type
IP20
volume
430W * 750D * 130H (2U)
weight
25.5 Kg
Guarantee
1 years
Communications and management
Interface type
USB/ smart card slot (dry card / dry contact extension card,
/SIC card, /Modbus card, /RS485 card)
Management software
SiteMonitor
Environment parameter
Operating temperature
0~40 DEG C
relative humidity
5~95%, no gel
Maximum elevation
<1500m, when exceeding 1500m, refer to GB/T 3859.2 derating
2.4 battery system
The key production technology and process specification of HUMBIRD (hummingbird) battery
HUMBIRD (hummingbird) VRLA battery is a new application of modern manufacturing technology, the company has strong technical force of scientific research, production, advanced testing equipment, strict organization and management in accordance with the ISO9002 international standard production. Product performance is stable and reliable, high quality, safe use and wide range of applications, through the national storage battery industry, South inspection center and other national designated units, testing, certification. Force valve controlled sealed lead-acid battery products are widely used in posts and telecommunications, finance, taxation, public security, electric power, hydropower, transportation and other departments.
Characteristic:
Seal: fully sealed design, no electrolyte leakage, transportation and installation are very convenient.
Safety: the battery has a safety valve, and is not easy to generate gas, fire will not explode, safety explosion-proof.
No maintenance: due to full seal design, production and basic
non decomposition of water,
Since use, no water maintenance is required.
Self discharge low: using new alloy, high-grade raw materials and advanced manufacturing process, storage at room temperature up to 6 months.
The use and storage of wide temperature range from 30 to 60 DEG C.
No equalization charge: under normal working conditions, constant voltage charging, no equalization charge.
Long service life: 25 DEG C under the condition of full floating normal service life of 6FM series of up to 5 years, GFM series of up to 10 years.
Use:
Posts and telecommunications equipment (program-controlled switches, microwave communications, mobile communications, optical fiber communications, etc.).
Large UPS and computer standby power supply (finance system, office equipment, computer room, etc.).
Power systems (power plants, hydropower stations, power plants, wind power and solar power plants).
Emergency lighting system, fire safety and alarm, monitoring
system, standby power supply.
Space, aviation, navigation, rail, road transportation and electrical energy storage.
Electronic switch and control system.
Peak load compensation energy storage device.
Advice on batteries:
Must:
Must be checked before using the battery appearance; storage battery in the shade (temperature preferably not more than 200C or 6800F); the store within three months of the battery to be added electric proper; charging should be carried out in a well ventilated environment; the battery is firmly installed on the equipment chassis
Be sure not to:
The battery is put in place near the fire or burning battery; battery circuit; the battery used in a closed box; rough handling battery; use lame crack or battery leakage; excessive vibration and shaking the battery
* formula of UPS battery power: P= (W * a) / (n * n)
The battery power unit - P, w / monomer (Watt/Cell);
WUPS power, this project uses 1 Emerson Adapt 10KVA UPS system;
Adapt 10KVA UPS AUPS power factor, power factor of 0.9;
N 2V battery monomer number, Adapt 10KVA UPS battery rated voltage according to 192V design, that is, n = 96;
Inverter efficiency - battery, Adapt UPS 0.97 10KVA;
From the above calculation parameters: P = (10000 x 0.9) / (96 * 0.97) = 96.65W/C (up and down to allow about 5% floating). Combined with the relevant file requirements, compared to the above constant power discharge data table, to determine the 10KVA load delay 2 hours, 12V65AH batteries need to be equipped with 2 groups, a total of 32.
Second pages, 12 pages