Quickbuilder点参数modbus地址格式
Defining a Modbus Address for a Point Parameter给一个点参数规定一个Modbus地址
Entering an Address访问一个地址
For PV Source Address, Source Address, and Destination Address the format for an Modbus
controller address is: 一个Modbus控制器地址的 PV源地址,源地址和目标地址格式 是:
Controlle...
Defining a Modbus Address for a Point Parameter给一个点参数规定一个Modbus地址
Entering an Address访问一个地址
For PV Source Address, Source Address, and Destination Address the format for an Modbus
controller address is: 一个Modbus控制器地址的 PV源地址,源地址和目标地址格式 是:
ControllerName Location控制器名字 位置
Part 部分
Description描述
ControllerName控制器名
The name of the Modbus controller. Modbus控制器的名字
Location 位置
The address within the controller where the value is stored. See Location Syntax.
这个值储存在控制器里的位置。查看 Location Syntax.
If you would like help when defining an address, click next to Address to display Address
Builder.
当你规定地址的时候如果你希望得到帮助的话,点击下一步去处理建立地址的显示
Using the Address Builder to Enter an Address用这个地址建立提示去建立地址
To specify a Modbus controller address, specify the items as follows: 制定一个Modbus控制器
地址,制定项目如下:
Property 性能
Description 描述
Address Type 地址类型
Select Controller.选择控制器
Controller 控制器
Select the appropriate Modbus controller. 选择一个适当的Modbus控制器
Location 位置
The address within the controller where the value is stored. See Location Syntax.
这个值储存在控制器里的位置。查看 Location Syntax.
Location Syntax 位置语法
The format for the location is:位置格式是:
Address [DataFormat|BitNumber] 地址[数据格式|字节数]
Part 部分
Description 描述
Address 地址
The address (decimal) for the parameter value within the controller table.
在控制器表格里参数值的地址
If the address is prefixed with the table number, omit the table number. For example, the first
register in table 4 is often written as 40001 or 400001. Enter 1 as the address.
如果位址与表数目一起前缀,省略表数目。例如,在表 4 里的第一个注册位置经常
被写成 40001 或者 400001.写 1 作为地址。
The table number prefix is shown on the Scanning tab of the Point Detail display and when you
use the commands listag, rtusum and lisscn.
前缀的桌面数被显示在点细节显示扫描界面 当你用 listag, rtusum 和 lisscn 命令时
DataFormat 点格式
The data format acronym or starting bit number, depending on how you want the value to be
read:
点格式的首字母缩写或者起始位数字,取决于你想用哪个值读取
Data Format for Scaling 16-bit Integers 16位整形缩放比例的点格式
Data Format for Reading Floating Point Values 浮点数的点格式
Data Format for Reading Raw Values Without Scaling 没有缺陷的不成熟点的数据格式
If you want to use a user-defined data format, you must define the format on the server. See the
Configuration Guide for details.
如果你想用一个用户自定义的点格式,你必须在服务器上定义这个格式,查看 the
Configuration Guide for details.
BitNumber 位数
Only applicable to Input Register and Holding Register data tables. The starting bit number,
ranging from 0 (default) to 15, where 0 is the right-most bit in the 16-bit register.
仅仅适用于输入寄存器和保持寄存器的数据表。起始位数从 0到 15,0在 16位里是最右边
的
Analog and accumulator point parameters can read up to 16 bits模拟和累加点是 16位.
Status point parameters read 1, 2 or 3 consecutive bits. 位参数读 1,2,或者 3连续
Example例如
Analog point模拟量点
PV source: 161 U4095 PV源:161 U4095
SP destination: 162 U4095 SP目标:162 U4095
Mode destination: 25 1 方式目的:25 1
Status point 状态点
PV source: 26 PV 来源:26
Accumulator point 累加点
PV source: 171 C16 PV来源:171 C16
Data Format for Scaling 16-bit Integers 16位整形资料格式
You can scale point parameter values with a data format if they have addresses in the Input
Register and Holding Register data tables. Select the format that corresponds to the counts that
have been set in the controller register.
Data Format
Counts in Controller Register
U4095 (default)
0 to 4095
U9999
0 to 9999
U999
0 to 999
U15B
0 to 32767
U16B
0 to 65535
S16B
-32768 to 32767
Note: If auxiliary parameters have a data format type that requires scaling (U4095, U999, and so
on), they take the same range as the PV.
Data Format for Scaling 32-bit Integers
The Modbus Interface will combine two 16-bit registers (as defined by the Modbus protocol
standard) into a 32-bit value.
The little-endian word formats listed in the following table.
Data Format
Description
Counts in Controller Register
S32B
Unsigned 32-bit Binary Little-endian
Not scaled
U32B
Unsigned 32-bit Binary Little-endian
Not scaled
S32BS
Signed 32-bit Binary Scaled Little-endian
-32768 to 32767
U32BS
Signed 32-bit Binary Scaled Little-endian
0 to 65535
These data formats assume the following word/byte order:
two 16-bit registers in big endian byte order
the first register transmitted is the low word
the second register transmitted is the high word
The value is calculated as (high register x 65536) + low register.
The big-endian word formats listed in the following table.
Data Format
Description
Counts in Controller register
U32BB
U32BSB
S32BB
Unsigned 32-bit Binary Big-endian
Not scaled
Unsigned 32-bit Binary Scaled Big-endian
0 to 65535
Signed 32-bit Binary Big-endian
Not scaled
S32BSB
Signed 32-bit Binary Scaled Big-endian
-32768 to 32767
These data formats assume the following word/byte order:
two 16-bit registers in big endian byte order
the first register transmitted is the high word
the second register transmitted is the low word
The value is calculated as (high register x 65536) + low register.
Data Format for Reading Floating Point Values
Select format IEEEFP to read two consecutive registers as a single precision floating point
number.
Variations on the IEEEFP format that you can specify include:
Format
Description
IEEEFPB
Bytes are big endian format (this is the same as IEEEFP)
IEEEFPBB
Bytes are byte-swapped big endian format
IEEEFPL
Bytes are little endian format
IEEEFPLB
Bytes are byte-swapped little endian format
Note
IEEEFP numbers use two data addresses, address and address-1. Do not specify address-1 (the
lower address) as the point parameter location address.
When configuring controller data tables, do not assign overlapping data addresses if floating
point values are used and do not set an IEEEFP address to 1.
Data Format for Reading Raw Values Without Scaling
Select a format of C16, or enter a 0, to read all 16 bits in the register without scaling.
To read less than 16 bits without scaling enter the starting bit number (1 to 15).
If you are not using scaling, the point range is still used for PV indicator bar height only (the PV
indicator bar is on the Point detail display on Station).
本文档为【Quickbuilder点参数modbus地址格式】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。