DS26C31T,DS26C32AM,DS26C32AT,
DS26F32MQML,DS26LS31C,DS26LS31M,
DS26LS32AC,DS26LS32C,DS26LS33M,
DS26LV31QML,DS26LV31T,DS26LV32AQML,
DS26LV32AT,DS34C86T,DS34C87T,DS34LV86T,
DS34LV87T
Application Note 903 A Comparison of Differential Termination Techniques
Literature Number: SNLA034A
A Comparison of
Differential Termination
Techniques
Introduction
Transmission line termination should be an important con-
sideration to the designer who must transmit electrical sig-
nals from any point A to any point B. Proper line termination
becomes increasingly important as designs migrate towards
higher data transfer rates over longer lengths of transmis-
sion media. However, the subject of transmission line termi-
nation can be somewhat confusing since there are so many
ways in which a signal can be terminated. Therefore, the
advantages and disadvantages of each termination option
are not always obvious.
The purpose of this application note is to remove some of the
confusion which may surround signal termination. This dis-
cussion, however, will focus attention upon signal termina-
tion only as it applies to differential data transmission over
twisted pair cable. Common differential signal termination
techniques will be presented and the advantages and disad-
vantages of each will be discussed.
Each discussion will also include a sample waveform gener-
ated by a setup consisting of a function generator whose
signals are transmitted across a twisted pair cable by a
differential line driver and sensed at the far end by a differ-
ential line receiver. This application note will specifically
address the following differential termination options:
• Unterminated
• Series/Backmatch
• Parallel
• AC
• Power (Failsafe)
• Alternate Failsafe
• Bi-Directional
For the purposes of discussion, popular TIA/EIA-422 drivers
and receivers, such as the DS26LS31 and DS26LS32A, will
be used to further clarify differential termination.
Unterminated
The selection of one termination option over another is of-
tentimes dictated by the performance requirements of the
application. The selection criteria may also hinge upon other
factors such as cost. From this cost perspective the option of
not terminating the signal is clearly the most cost effective
solution. Consider Figure 1, where a DS26LS31 differential
driver and a DS26LS32A differential receiver have been
connected (using a twisted pair cable) together without a
termination element. Because there is no signal termination
element, the DS26LS31 driver’s worst case load is the
DS26LS32A receiver’s minimum input resistance.
Since, TIA/EIA-422-A (RS-422) standard defines the
DS26LS32A’s minimum input resistance to be 4 kΩ, the
driver’s worst case load, as seen in Figure 1, is then 4 kΩ.
In the unterminated configuration, the DS26LS31 driver is
only required to source a minimal amount of current in order
to drive a signal to the receiver. This minimal DC current
sourcing requirement in turn minimizes the driver’s on chip
power dissipation. In addition, the 4 kΩ driver output load
results in a higher driver output swing (than if the driver was
loaded with 100Ω) which in turn increases DC noise margin.
This increase in noise margin further diminishes the possi-
bility that system noise will improperly switch the receiver. To
be sure that there is no confusion, noise margin is defined as
the difference between the minimum driver output swing and
the maximum receiver sensitivity. On the other hand, if a
receiver was used which complies to TIA/EIA-485 (RS-485),
the resulting noise margin would be even greater. This is
because the minimum input resistance of an RS-485 re-
ceiver must be greater than 12 kΩ as compared to 4 kΩ for
an RS-422 receiver.
The absence of a termination element at the DS26LS32A’s
inputs also guarantees that the receiver output is in a known
logic state when the transmission line is in the idle or open
line state (receiver dependent). This condition is commonly
referred to as open input receiver failsafe. This receiver
failsafe (Note 1) bias is guaranteed by internal pull up and
pull down resistors on the positive and negative receiver
inputs, respectively. These pull up and pull down resistors
bias the input differential voltage (VID) to a value greater than
200 mV when the line is, for example, idle (un-driven). This
bias is significant in that it represents the minimum guaran-
teed VID required to switch the receiver output into a logic
high state.
Note: A complete discussion of receiver failsafe can be found in Application
Note 847 (AN-847).
There are, however, some disadvantages with an untermi-
nated cable. The most significant effect of unterminated data
transmission is the introduction of signal reflections onto the
transmission line. Basic transmission line theory states that
a signal propagating down a transmission line will be re-
flected back towards the source if the outbound signal en-
counters a mismatch in line impedance at the far end. In the
case of Figure 1, the mismatch occurs between the charac-
teristic impedance of the twisted pair (typically 100Ω) and
the 4 kΩ input resistance of the DS26LS32A. The result is a
signal reflection back towards the driver. This reflection then
encounters another impedance mismatch at the driver out-
puts which in turn generates additional reflections back to-
ward the receiver, and so on. The net result is a number of
reflections propagating back and forth between the driver
and receiver. These reflections can be observed in Figure 2.
01189801
FIGURE 1. Unterminated Configuration
National Semiconductor
Application Note 903
Joe Vo
August 1993
A
Com
parison
ofDifferentialTerm
ination
Techniques
AN-903
© 2002 National Semiconductor Corporation AN011898 www.national.com
Unterminated (Continued)
The main limitation of unterminated signals can be clearly
seen in Figure 2. A positive reflection is generated when the
signal encounters the large input resistance of the receiver.
These reflections propagate back and forth until a steady
state condition is reached after several round trip cable
delays. The delay is a function of the cable length and the
cable velocity. Figure 2 shows that the reflections settle after
three round trips. To limit the effect of these reflections,
unterminated signals should only be used in applications
with low data rates and short driving distances.
The data being transmitted should, therefore, not make any
transitions until after this steady state condition has been
reached. A low data rate ensures that reflections have suffi-
cient time to settle before the next signal transition. At the
same time, a short cable length ensures that the time re-
quired for the reflections to settle is kept to a minimum. The
low data rate and short cable length dictated by the lack of
termination is probably the most significant shortcoming of
the unterminated option.
Low speed is generally characterized to be either signalling
rates below 200 kbits/sec or when the cable delay (the time
required for an electrical signal to transverse the cable) is
substantially shorter than the bit width (unit interval) or when
the signal rise time is more than four times the one way
propagation delay of the cable (i.e., not a transmission line).
As a general rule, if the signal rise time is greater than four
times the propagation delay of the cable, the cable is no
longer considered a transmission line.
It should be mentioned that most differential data transmis-
sion applications provide for some kind of signal termination.
This is because most differential applications transmit data
at relatively high transfer rates over relatively long distances.
In these type of applications, signal termination is critically
important. If the application only requires low speed opera-
tion over short distances, an unterminated transmission line
may be the simplest solution.
Series Termination
Another termination option is popularly known as either se-
ries or backmatch termination. Figure 3 illustrates this type of
termination. The termination resistors, RS, are chosen such
that their value plus the impedance of the driver’s output
equal the characteristic impedance of the cable. Now as the
01189802
FIGURE 2. Unterminated Waveforms
AN
-9
03
www.national.com 2
Series Termination (Continued)
driven signal propagates down the transmission line an im-
pedance mismatch is still encountered at the far end of the
cable (receiver inputs).
However, when that signal propagates back to the driver the
reflection is terminated at the driver output. There is only one
reflection before the driven signal reaches a steady state
condition. How long it takes for the driven signal to reach
steady state is still dependent upon the length of cable the
signal must traverse. As with the unterminated option the
driver power dissipation is still minimized due to the light
loading presented by the 4 kΩ receiver input resistance. The
driver loading remains unchanged from the unterminated
option. In both cases the driver is effectively loaded with the
receiver’s input impedance. DC noise margin has again
increased and the open input receiver failsafe feature is still
supported for idle and open line conditions.
There are three major disadvantages in using series termi-
nation. First, the driver output impedances can vary, due to
normal process variations, from one manufacturer to another
and from one driver load to another. Should there be a
problem which involves replacing line drivers, there is a
chance that the designer might have to rework the board in
order to ensure that the RS matches the new driver’s output
impedance.
Second, series termination is commonly limited to only point
to point applications. Consider the following example. If a
second receiver (multidrop application) was located halfway
between the driver and receiver at the far end of the cable,
the noise margin seen by the middle receiver would change
between the incident signal and the reflected signal. Such a
problem would not exist in a point to point application where
only one receiver is used with one driver.
Third, there is still an impedance mismatch at the receiver
inputs. Again, this mismatch is caused by a signal propagat-
ing down a 100Ω cable suddenly encountering a 4 kΩ re-
ceiver input resistance. This impedance mismatch will con-
tinue to cause reflections on the transmission line as
illustrated in Figure 4.
Notice the reflections which result when the driven signal
encounters an impedance mismatch at the receiver input.
The reflection propagates back to the driver and is some-
what terminated by the driver’s output impedance. The re-
flected signal is terminated because the combined imped-
ance of the series resistor (RS) and the driver’s output
impedance comes close to matching the characteristic im-
pedance of the cable. In contrast with Figure 2’s untermi-
nated signal waveform, the waveform seen in Figure 4 is
characterized by only one reflection.
In all it will take the signal one round trip cable delay to be
reflected back towards the signal source. Since all reflec-
tions should be allowed to settle before the next data tran-
01189803
FIGURE 3. Series Termination Configuration
01189804
FIGURE 4. Series Termination Waveforms
AN-903
www.national.com3
Series Termination (Continued)
sition (to maintain data integrity), it is imperative that the
round trip cable delay be kept much less than the time unit
interval (TUI — defined to be the minimum bit width or the
“distance” between signal transitions). In other words, series
termination should be limited to applications where the cable
lengths are short (to minimize round trip cable delays) and
the data rate is low (to maximize the TUI). And to a lesser
degree, the series termination option may not be the ideal
choice from a cost perspective in that it requires two addi-
tional external components.
Parallel Termination
Parallel termination is arguably one of the most prevalent
termination schemes today. In contrast to the series termi-
nation option, parallel termination employs a resistor across
the differential lines at the far (receiver) end of the transmis-
sion line to eliminate all reflections. See Figure 5.
Eliminating all reflections requires that RT be selected to
match the characteristic impedance (ZO) of the transmission
line. As a general rule, however, it is usually better to select
RTsuch that it is slightly greater than ZO. Over-termination
tends to be more desirable than under-termination since
over-termination has been observed to improve signal qual-
ity. RT is typically chosen to be equal to ZO. When
over-termination is used RT is typically chosen to be up to
10% larger than ZO. The elimination of reflections permits
higher data rates over longer cable lengths. Keep in mind,
however, that there is an inverse relationship between data
rate and cable length. That is, the higher the data rate the
shorter the cable and conversely the lower the data rate the
longer the cable. Higher data rates and longer cable lengths
translate simply into smaller TUI’s and longer cable delays.
Unlike series termination where high data rates and long
cable lengths can negatively impact data integrity, parallel
termination can effectively remove all reflections; thereby
removing all concerns about reflections interfering with data
transitions. See Figure 6.
01189805
FIGURE 5. Parallel Termination Configuration
AN
-9
03
www.national.com 4
Parallel Termination (Continued)
As seen in Figure 6 both driver output and receiver input
signals are free of reflections. Such results make parallel
termination optimal for use in either high speed (10 Mb/s), or
long cable length (up to 4000 feet), applications.
Another benefit the parallel termination provides is that both
point to point and multidrop applications are supported. Re-
call that multidrop is defined as a distribution system com-
posed of one driver and up to ten receivers spread out along
the cable as defined in the TIA/EIA-422 standard. The par-
allel termination is located at the far end (opposite the driver)
of the cable and effectively terminates the signal at that
location, preventing reflections.
There are also disadvantages to parallel termination. Let’s
examine these disadvantages as they pertain to multidrop
configurations. An intrinsic assumption to multidrop opera-
tion is that stub lengths, as measured by “I” in Figure 5, are
minimized. Despite the fact that all receivers are effectively
terminated with RT, long stub lengths will once again reintro-
duce impedance mis-matches and reflections. So while par-
allel termination may remove reflections and permit multi-
drop configurations, it does place a restriction upon the stub
lengths associated with these other receivers. Typically
stubs should be kept to less that 1⁄4 of the drivers rise time in
length to minimize transmission line effects, and reflections.
TIA/EIA-422-A standard does recommend a 100Ω resistor to
be used when the differential line is parallel terminated.
Therefore, applications which use a TIA/EIA-422-A driver
such as the DS26LS31 or DS26C31 are commonly termi-
nated with 100Ω at the far end of the twisted pair cable.
While the 100Ω parallel termination eliminates all reflections,
the power dissipated by the driver will increase substantially
with the addition of this resistor. This increased driver power
dissipation is a major disadvantage of parallel termination.
The absence of this termination resistor keeps driver power
dissipation low for unterminated and series terminated driv-
ers and is a major advantage of these two termination op-
tions.
Noise margin will also decrease with parallel termination.
The relatively light loading (4 kΩ) of unterminated and series
terminated drivers led to larger driver output swings. The
heavier driver Ioad (typically 100Ω) brought on by parallel
termination reduces the driver’s output signal swing. How-
ever, even with this reduction, there is ample noise margin
left to ensure that the receiver does not improperly switch.
Recall the discussion earlier about receiver failsafe with the
unterminated and series options. In both cases, open input
receiver failsafe operation was guaranteed because of inter-
nal circuitry (receiver dependent) which biases the differen-
01189806
FIGURE 6. Parallel Termination Waveforms
AN-903
www.national.com5
Parallel Termination (Continued)
tial input voltage (VID) to a value greater than its differential
threshold. Since the resulting bias voltage at the receivers
inputs (VID), is greater than +200 mV, the output of the
DS26LS32A receiver remains in a stable HIGH state. Unlike
unterminated and series options, parallel termination cannot
support open input receiver failsafe when the transmission
line is in the idle state. This shortcoming of parallel termina-
tion is discussed in much greater detail later in the section
which describes power and alternate failsafe termination
(see AN-847 for more of information on failsafe biasing
differential buses).
AC Termination
The effectiveness of parallel termination is oftentimes coun-
tered by increased driver power dissipation and receiver
failsafe concerns. The DC loop current required by the ter-
mination resistor, RT (see Figure 5), is often too large in
order to be useful for power conscious applications or for
seldomly switched control lines. In asynchronous applica-
tions, parallel termination’s is not able to guarantee receiver
failsafe during idle bus states which in turn makes the sys-
tem susceptible to errors such as false start bits and framing
errors. The primary reason for the AC termination, however,
grew out of the need for effective transmission line termina-
tion with minimal DC loop current.
A representation of an AC terminated differential line is
shown in Figure 7.
The value of RT generally ranges from 100Ω–150Ω (cable
ZO dependent) and is selected to match the characteristic
impedance (ZO) of the cable. CT, on the other hand, is
selected to be equal to the round trip delay of the cable
divided by the cable’s ZO.
EQ1: CT ≤ (Cable round trip delay) / ZO
For this example:
Cable Length = 100 feet
Velocity = 1.7 ns/foot
Char. Impedance = 100Ω
Therefore,
CT ≤ (100 ft x 2 x 1.7 ns/ft)/100Ω or ≤ 3,400 pF.
Further, the resulting RC time constant should be less than or
equal to 10% of the unit interval (TUI). In the example
provided the maximum switching rate therefore should be
less than 300 kHz. This termination should now behave like
a parallel termination during transitions, but yield the ex-
panded noise margins during steady state conditions. See
Figure 8.
Figure 8 illustrates the tradeoff between parallel terminated
and unterminated signals. There are no major reflections
and driver power dissipation is reduced at the expense of a
low pass filtering effect which essentially limits the applica-
tion of AC termination to low speed control lines. Note that
the frequency of the driven signal in Figure 8 is 300 kHz
whereas it was 500 kHz for the other plots. This was done to
maintain the ratio between bit time and the RC time constant.
The draft revision of RS-422-A will include AC termination as
an alternative to paralleI termination.
01189807
FIGURE 7. AC Termination Configuration
AN
-9
03
www.national.com 6
AC Termination (Continued)
The waveforms in Figure 8 should be viewed together with
the following brief explanation of how AC termination works.
When the driven signal transitions from one logic state to
another, the capacitor CT behaves as a short circuit and
consequently, the load presented to the driver is essentially
RT. However, once the driven signal reaches its intended
levels, either a logic HIGH or logic LOW, CT will behave as
an open circuit. DC loop current is now blocked. The driver
power dissipation will then decrease. The load presented to
the driver also decreases. This is due to the fact that the
driver is n
本文档为【差分电路终端接法比较】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。