TI096R/09/en
No. 51004792
Technical information
iTEMP® TC TMT128
DIN rail mounted Temperature Transmitter for Thermocouples
(TC)
â Ó 4
0 1 2
Application
• Temperature transmitter with fixed measuring ranges
for converting TC input signals into an analogue,
scalable 4 to 20 mA output signal
• Input:
Thermocouples (TC)
Features and benefits
• High accuracy: 0.08 % of span
• Breakdown information in event of sensor break or
sensor short-circuit enables a quick maintenance
intervention
• Galvanic isolation 2 kV (from the sensor input to the
output)
• Long term stability: < 0.05 %/year
• Electromagnetic compatibility to IEC 61326 for use in
noisy environments
• Ex approvals for high safety standards:
- ATEX EEx ia, nA
- CSA IS, NI
- CSA GP
- FM IS, NI
• GL Germanische Lloyd / marine approval
• UL recognized component to UL 3111-1
TMT128
2 Endress+Hauser
Function and system design
Measuring principle Electronic acquisition and conversion of input signals in industrial temperature measurement.
Measuring system The iTEMP® TC TMT128 DIN rail temperature transmitter is a two-wire transmitter with analogue output
and measuring input for thermocouples.
Input values
Measured variable Temperature
Measuring range Depending on the application, different measuring ranges can be ordered (see ’Product structure’).
Input type
Output
Output signal Analog 4 to 20 mA
Breakdown information Breakdown information to NAMUR NE 43
Breakdown information is created when the measuring information is invalid or not present anymore and gives
a complete listing of all errors occuring in the measuring system.
Source impedance Max. (Vpower supply- 12V) / 0.022 A (current output)
e. g. (24 V - 12 V)/0.022 A = 545.5 Ω
Transmission behavior Temperature linear
Galvanic isolation U = 2 kV AC (input/output)
Input Designation Measuring range limits Min. span
Thermocouples (TC)
B (PtRh30-PtRh6)
C (W5Re-W26Re)1
D (W3Re-W25Re)1
E (NiCr-CuNi)
J (Fe-CuNi)
K (NiCr-Ni)
L (Fe-CuNi)2
N (NiCrSi-NiSi)
R (PtRh13-Pt)
S (PtRh10-Pt)
T (Cu-CuNi)
U (Cu-CuNi)2
to IEC 60584 part 1
1) to ASTM E988
2) to DIN 43710
0 to +1820 °C (32 to 3308 °F)
0 to +2320 °C (32 to 4208 °F)
0 to +2495 °C (32 to 4523 °F)
-270 to +1000 °C (-454 to 1832 °F)
-210 to +1200 °C (-346 to 2192 °F)
-270 to +1372 °C (-454 to 2501 °F)
-200 to +900 °C (-328 to 1652 °F)
-270 to +1300 °C (-454 to 2372 °F)
-50 to +1768 °C (-58 to 3214 °F)
-50 to +1768 °C (-58 to 3214 °F)
-270 to +400 °C (-454 to 752 °F)
-200 to +600 °C (-328 to 1112 °F)
500 K
500 K
500 K
50 K
50 K
50 K
50 K
50 K
500 K
500 K
50 K
50 K
• Internal cold junction (Pt100)
• Accuracy of cold junction: ±1 K
• Sensor current: = 350 nA
Signal (mA)
Under ranging Standard 3.8
Over ranging Standard 20.5
Sensor break; sensor short circuit To NAMUR NE 43 ≥ 21.0
TMT128
Endress+Hauser 3
Induced current requirement ≤ 3.5 mA
Current limitation ≤ 23 mA
Switch-on delay 4 s (during switch-on procedure Ia ≤ 3.8 mA)
Power supply
Electrical connection
Temperature transmitter terminal assignment
Supply voltage Ub= 12 to 35 V, reverse polarity protection
Residual ripple Permitted residual ripple Uss ≤ 3V at Ub ≥ 15V, fmax. = 1 kHz
Accuracy
Response time 1 s
Reference operating
conditions
Calibration temperature: +25 °C (77 °F) ± 5 K
Maximum measured error
Influence of supply voltage • ≤ ±0.01%/V deviation from 24 V
Percentages refer to the full scale value.
Influence of ambient
temperature (temperature
drift)
• Thermocouple (TC):
Td= ±(50 ppm/K * max. measuring range + 50 ppm/K * of set measuring range) * Δ ϑ
Δ ϑ = deviation of the ambient temperature from the reference operating condition (25 °C (77 °F) ± 5 K).
Influence of load • ± 0.02%/100 Ω
Values refer to the full scale value.
Long-term stability • ≤ 0.1 K/year or ≤ 0.05%/year
Designation Accuracy1
1) % refer to the set span. The highest value is valid.
Thermocouples (TC)
K, J, T, E, L, U
N, C, D
S, B, R
typ. 0.5 K or 0.08%
typ. 1.0 K or 0.08%
typ. 2.0 K or 0.08%
TMT128
4 Endress+Hauser
Values under reference operating conditions. % refer to the set span. The larger value applies.
Installation conditions
Installation instructions Installation location
No restrictions
Environmental conditions
Ambient temperature
limits
-40 to +85 °C (-40 to 185 °F), for Ex-area, see Ex-certificate
Storage temperature -40 to +100 °C (-40 to 212 °F)
Climate class As per IEC 60654-1, Class C
Degree of protection IP 20
Shock resistance 4g / 2 to 150 Hz as per IEC 60068-2-6
Vibration resistance see ’Shock resistance’
Electromagnetic
compatibility (EMC)
Shock resistance and interference emission as per IEC 61326 and NAMUR NE 21.
Condensation permitted
Mechanical construction
Design, dimensions
Values in inch (mm)
Weight approx. 90 g (3.18 oz)
TMT128
Endress+Hauser 5
Material Housing: PC/ABS, UL 94V0
Terminals Pluggable screw terminal, max. 2,5 mm2 (0.0039 in2) solid, or strand with wire end sleeve.
Human interface
Display elements Illuminated yellow LED (2 mm, 0.08 in) signals device operation.
Operating elements There are no operating elements available on the device.
Certificates and approvals
CE-Mark The device meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has
been successfully tested by applying the CE mark.
Hazardous area approvals For further details on the available Ex versions (ATEX, CSA, FM, etc.), please contact your nearest E+H sales
organisation. All relevant data for hazardous areas can be found in separate Ex documentation. If required,
please request copies from us or your E+H sales organisation.
GL Ship building approval (Germanischer Lloyd)
Other standards and
guidelines
• IEC 60529:
Degree of protection provided by housing (IP-Code)
• IEC 61010:
Safety requirements for electrical measurement, control and laboratory use.
• IEC 61326:
Electromagnetic compatibility (EMC requirements)
• NAMUR
Standards working group for measurement and control technology in the chemical industry.
(www.namur.de)
UL Recognized component to UL 3111-1
Ordering information
Product structure TMT128 iTEMP TC DIN rail TMT128
for temperature measurement with TC
Analog output 4 to 20 mA; 2-wire techn.; Galvanic isolation; Failure mode to NAMUR NE 43; 22.5 mm wide; for 35 mm top
hat DIN rail according to IEC 60715; UL recognized, ship building approval GL
Approval
A Version for non hazardous areas
B ATEX II2(1)G EEx ia IIC T4/T5/T6
C FM IS,NI,Class I,Div.1+2,Group ABCD
D CSA IS,NI,Class I,Div.1+2,Group ABCD
E ATEX II3G EEx nA IIC T4/T5/T6
I FM+CSA IS,NI,Class I,Div.1+2,Group ABCD
J CSA General Purpose
Temperature sensor
B Type B ( 400 to 1820 °C, 752 to 3308 °F, min. span 500 K)
C Type C ( 500 to 2320 °C, 932 to 4208 °F, min. span 500 K)
D Type D ( 500 to 2495 °C, 932 to 4523 °F, min. span 500 K)
E Type E (-200 to 1000 °C, -328 to 1832 °F, min. span 50 K)
J Type J (-200 to 1200 °C, -328 to 2192 °F, min. span 50 K)
K Type K (-200 to 1372 °C, -328 to 2501 °F, min. span 50 K)
TMT128
6 Endress+Hauser
Accessories
No accessories are required for this device.
Documentation
Brochure ’Temperature measurement’ (FA006T09en)
Operating short manual “iTEMP® RTD/TC DIN rail TMT127/128“ (KA140R09a3)
Ex-Supplementary documentation: ATEX Safety instructions II2(1)G (XA013R09a3)
and II3G (XA018R09a3)
L Type L (-200 to 900 °C, -328 to 1652 °F, min. span 50 K)
N Type N (-100 to 1300 °C, -148 to 2372 °F, min. span 50 K)
R Type R ( -50 to 1768 °C, -58 to 3214 °F, min. span 500 K)
S Type S ( -50 to 1768 °C, -58 to 3214 °F, min. span 500 K)
T Type T (-200 to 400 °C, -328 to 752 °F, min. span 50 K)
U Type U (-200 to 600 °C, -328 to 1112 °F, min. span 50 K)
Measuring Range
AA 0 to 100 °C (32 to 212 °F)
AB 0 to 150 °C (32 to 302 °F)
AC 0 to 250 °C (32 to 482 °F)
AD 0 to 400 °C (32 to 752 °F)
AE 0 to 600 °C (32 to 1112 °F)
AF 0 to 900 °C (32 to 1652 °F)
AG 0 to 1000 °C (32 to 1832 °F)
AH 0 to 1200 °C (32 to 2192 °F)
AI 0 to 1400 °C (32 to 2552 °F)
AJ 0 to 1600 °C (32 to 2912 °F)
AK 0 to 200 °C (32 to 392 °F)
AL 0 to 300 °C (32 to 575 °F)
AM 0 to 500 °C (32 to 932 °F)
DE -10 to 200 °C (14 to 392 °F)
JA -50 to 200 °C (-58 to 392 °F)
LA -40 to 140 °F
NA 0 to 100 °F
NB 0 to 200 °F
NC 0 to 300 °F
ND 0 to 500 °F
NE 0 to 750 °F
NG 0 to 1000 °F
NI 0 to 1500 °F
NK 0 to 2500 °F
NL 0 to 3200 °F
Additional Option
A Standard model
B Works calibration certificate (6 test points)
K Standard model, North American region
TMT128- ⇒ Order code (complete)
Temperature sensor
iTEMP TC TMT128 1
iTEMP TC TMT128 2
iTEMP TC TMT128 3
iTEMP TC TMT128 4
iTEMP TC TMT128 5
iTEMP TC TMT128 6
iTEMP TC TMT128 7
本文档为【德国E+H温度仪表:温度变送器 iTEMP TC TMT128】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。