TI090R/09/en
51003953
Temperature transmitter
iTEMP® HART® DIN rail TMT122
Universal temperature transmitter for resistance thermometers
(RTD), thermocouples, resistance and voltage transmitters,
incorporating HART® protocol
Application areas
• Temperature transmitter with HART® protocol for
converting various input signals into a scalable
4 to 20 mA analogue output signal
• Input:
Resistance thermometer (RTD)
Thermocouple (TC)
Resistance transmitter (Ω)
Voltage transmitter (mV)
• HART® protocol for front end unit or panel unit
operation using the hand operating module (DXR275,
DXR375) or PC (e.g. ReadWin® 2000 or FieldCare)
• Installation on DIN rail according to IEC 60715
Features and benefits
• Universal settings with HART® protocol for various
input signals
• 2-wire technology, 4 to 20 mA analogue output
• High accuracy in total ambient temperature range
• Fault signal on sensor break or short circuit,
presettable to NAMUR NE 43
• EMC to NAMUR NE 21, CE
• UL recognized component to UL 3111-1
• Ex-Certification:
- ATEX Ex ia
- CSA IS
- FM IS
• Ship building approval GL
• Galvanic isolation
• Output simulation
• Min./max. process value indicator function
• Customer-specific linearisation
• Linearisation curve match
• Customer-specific measurement range settings or
expanded SETUP (see Questionnaire, page 7)
0 2 1 â Ó
TMT122
2 Endress+Hauser
Operation and system construction
Measurement principle Electronic measurement and conversion of input signals in industrial temperature measurement.
Measurement system The iTEMP® HART® DIN rail TMT122 temperature transmitter is a 2-wire transmitter with an analogue
output. It has measurement input for resistance thermometers (RTD) in 2-, 3- or 4-wire connection, thermo-
couples and voltage transmitters. Setting up of the TMT122 is done using the HART® protocol with hand
operating module (DXR275, DXR375) or PC (e.g. configuration software ReadWin® 2000 or FieldCare).
Input
Measured variable Temperature (temperature linear), resistance and voltage.
Measuring range Depending upon the sensor connection and input signal. The transmitter evaluates a number of different meas-
urement ranges.
Type of input
Resistance
thermometer (RTD)
Type Measurement ranges Min. measurement range
Pt100
Pt500
Pt1000
acc. to IEC 751 (α = 0.00835)
Pt100
acc. to JIS C 1604-81 (α = 0.003916)
-200 to 850 °C (-328 to 1562 °F)
-200 to 250 °C (-328 to 482 °F)
-200 to 250 °C (-238 to 482 °F)
-200 to 649 °C (-328 to1200 °F)
10 K
10 K
10 K
10 K
Ni100
Ni500
Ni1000
acc. to DIN 43760 (α = 0.006180)
-60 to 250 °C (-76 to 482 °F)
-60 to 150 °C (-76 to 302 °F)
-60 to 150 °C (-76 to 302 °F)
10 K
10 K
10 K
• Connection type: 2-, 3- or 4-wire connection
• Software compensation of cable resistance possible in the 2-wire system (0 to 30 Ω)
• Sensor cable resistance max. 40 Ω per cable
• Sensor current: ≤ 0.2 mA
Resistance transmitter Resistance Ω 10 to 400 Ω
10 to 2000 Ω
10 Ω
100 Ω
Thermocouples (TC)
B (PtRh30-PtRh6)
C (W5Re-W26Re)a
D (W3Re-W25Re)a
E (NiCr-CuNi)
J (Fe-CuNi)
K (NiCr-Ni)
L (Fe-CuNi)b
N (NiCrSi-NiSi)
R (PtRh13-Pt)
S (PtRh10-Pt)
T (Cu-CuNi)
U (Cu-CuNi)b
0 to +1820 °C (32 to 3308 °F)
0 to +2320 °C (32 to 4208 °F)
0 to +2495 °C (32 to 4523 °F)
-270 to +1000 °C (-454 to 1832 °F)
-210 to +1200 °C (-346 to 2192 °F)
-270 to +1372 °C (-454 to 2501 °F)
-200 to +900 °C (-328 to 1652 °F)
-270 to +1300 °C (-454 to 2372 °F)
-50 to +1768 °C (-58 to 3214 °F)
-50 to +1768 °C (-58 to 3214 °F)
-270 to +400 °C (-454 to 752 °F)
-200 to +600 °C (-328 to 1112 °F)
500 K
500 K
500 K
50 K
50 K
50 K
50 K
50 K
500 K
500 K
50 K
50 K
• Cold junction internal (Pt100)
• Cold junction accuracy: ± 1 K
Voltage transmitters Millivolt transmitter -10 to 75 mV 5 mV
a. According to ASTM E988
b. According to DIN IEC 584 part 1
TMT122
Endress+Hauser 3
Output
Output signal Analogue 4 to 20 mA, 20 to 4 mA
Signal on alarm • Measurement range undercut:
Linear drop to 3.8 mA
• Exceeding measurement range:
Linear rise to 20.5 mA
• Sensor breakage; Sensor short circuit1:
≤ 3.6 mA or ≥ 21.0 mA (if setting ≥ 21.0 mA the output is > 21.5 mA)
Load Max. (VPower supply - 12 V) / 0.022 A (Current output)
Linearisation / transmission
behaviour
Temperature linear, resistance linear, voltage linear
Filter Digital filter 1. degree: 0 to 100 s
Galvanic isolation U = 2 kV AC (Input/output)
min. current consumption ≤ 3.5 mA
Current limit ≤ 23 mA
Switch on delay 4 s (during power up Ia ≈ 3.8 mA)
Auxiliary energy
Electrical connection
Temperature transmitter terminal connections
For the unit operation via HART® communication sockets a minimum load resistance of 250 Ω is necessary
in the signal circuit!
Power supply Ub = 12 to 35 V, polarity protected
Residual ripple Allowable ripple Uss ≤ 3 V at Ub ≥ 15 V, f max. = 1 kHz
1. Not for thermocouple
T0
9-
TM
T1
22
-0
4-
10
-X
X-
en
-0
01
.e
ps
TMT122
4 Endress+Hauser
Performance characteristics
Response time 1 s
Reference operating
conditions
Calibration temperature: +23 °C ± 5 K (73.4 °F ± 9 °F)
Maximum measured error
Influence of power supply ≤ ± 0.01%/V deviation from 24 V1
Influence of ambient
temperature (temperature
drift)
• Resistance thermometer (RTD):
Td = ± (15 ppm/K * max. meas. range + 50 ppm/K * preset meas. range) * ∆ ϑ
• Resistance thermometer Pt100:
Td = ± (15 ppm/K * (range end value + 200) + 50 ppm/K * preset meas. range) * ∆ ϑ
• Thermocouple (TC):
Td = ± (50 ppm/K * max. meas. range + 50 ppm/K * preset meas. range) * ∆ ϑ
∆ ϑ = Deviation of the ambient temperature according to the reference condition (+23 °C ± 5 K or
73.4 °F ± 9 °F).
Long term stability ≤ 0.1K/Year2 or ≤ 0.05%/Year2 3
Influence of load ≤ ±0.02%/100 Ω1
Influence of cold junction Pt100 DIN IEC 751 Cl. B (internal reference junction for thermocouples TC)
Installation conditions
Installation instructions Orientation
No limit
Type Measurement accuracy3
Resistance thermometer RTD
Pt100, Ni100
Pt500, Ni500
Pt1000, Ni1000
0.2 K (0.36 °F) or 0.08%
0.5 K (0.9 °F) or 0.20%
0.3 K (0.54 °F) or 0.12%
Thermocouple TC
K, J, T, E, L, U
N, C, D
S, B, R
typ. 0.5 K (0.9 °F) or 0.08%
typ. 1.0 K (1.8 °F) or 0.08%
typ. 2.0 K (3.6 °F) or 0.08%
Measurement range Measurement accuracy3
Resistance transmitter (Ω) 10 to 400 Ω
10 to 2000 Ω
± 0.1 Ω or 0.08%
± 1.5 Ω or 0.12%
Voltage transmitter (mV) -10 to 75 mV ± 20 µV or 0.08%
1. All data is related to a measurement end value
2. According to reference conditions
3. % is related to the adjusted measurement range (the value to be applied is the greater one).
TMT122
Endress+Hauser 5
Environment conditions
Ambient temperature range Preferably reference conditions
Ambient temperature limits −40 to +85 °C (-40 to +185 °F) for Ex-area, see Ex-certification
Storage temperature -40 to +100 °C (-40 to +212 °F)
Climate class According to EN 60 654-1 (IEC 60654-1), Class C
Ingress protection IP 20
Electromagnetic
compatibility (EMC)
Interference immunity and interference emission according to EN 61 326-1 (IEC 1326) and NAMUR NE 21
Condensation Permitted
Shock and vibration resistance 4g / 2 to 150 Hz as per IEC 60 068-2-6
Mechanical construction
Design, dimensions
Housing for DIN rail mounting according to IEC 60715; Dimensions in mm (inches)
Weight Approx. 90 g (3.2 oz)
Material Housing: Plastic PC/ABS, UL 94V0
Terminals Keyed plug-in screw terminals, core size max. 2.5 mm² (16 AWG) solid, or strands with ferrules
T0
9-
TM
T1
22
-0
6-
10
-X
X-
en
-0
02
.e
ps
TMT122
8 Endress+Hauser
Product structure
Accessories
Commubox FXA191, PC operating software ReadWin® 2000 or FieldCare
Certification
A Version for non Ex areas
B ATEX II 2(1) G EEx ia IIC T4/T5/T6
C FM IS, Class I, Div. 1+2, Group A, B, C, D
D CSA IS, Class I, Div. 1+2, Group A, B, C, D
E ATEX II3G EEx nA IIC T4/T5/T6
I FM+CSA IS, NI, Class I, Div. 1+2, Group A, B, C, D
J CSA General Purpose
Configuration transmitter connection
A Standard factory configuration
1 Configuration connection TC
2 Configuration connection RTD 2-wire
3 Configuration connection RTD 3-wire
4 Configuration connection RTD 4-wire
Configuration temperature sensor
A Standard factory configuration
B Config. Typ B (0 to 1820 °C min. span 500 K)
C Config. Typ C (0 to 2320 °C min. span 500 K)
D Config. Typ D (0 to 2495 °C min. span 500 K)
E Config. Typ E (-200 to 1000 °C min. span 50 K)
J Config. Typ J (-200 to 1200 °C min. span 50 K)
K Config. Typ K (-200 to 1372 °C min. span 50 K)
L Config. Typ L (-200 to 900 °C min. span 50 K)
N Config. Typ N (-270 to 1300 °C min. span 50 K)
R Config. Typ R (-0 to 1768 °C min. span 500 K)
S Config. Typ S (-0 to 1768°C min. span 500 K)
T Config. Typ T (-200 to 400 °C min. span 50 K)
U Config. Typ U (-200 to 600 °C min. span 50 K)
1 Config. Pt100
acc. to IEC751
(-200 to 850 °C min. span 10 K)
2 Config. Ni100 (-60 to 180 °C min. span 10 K)
3 Config. Pt500 (-200 to 250 °C min. span 10 K)
4 Config. Ni500 (-60 to 150 °C min. span 10 K)
5 Config. Pt1000 (-200 to 250 °C min. span 10 K)
6 Config. Ni100 (-60 to 150 °C min. span 10 K)
9 Config. Pt100 acc. to
JIS C1604-81
(-200 to 649 °C min. span 10 K)
Setup
A Standard factory configuration (Pt100/3-wire/0 to 100 °C)
B Customised measurement range
C Customised expanded configuration for TC (see questionnaire)
D Customised expanded configuration for RTD (see questionnaire)
Model
A Standard model
B Works calibration certificate 6 test points
TMT122- ⇐ Order code
iTEMP HART TMT122 1
iTEMP HART TMT122 2
iTEMP HART TMT122 3
iTEMP HART TMT122 4
iTEMP HART TMT122 5
iTEMP HART TMT122 6
iTEMP HART TMT122 7
本文档为【德国E+H温度仪表:温度变送器 iTEMP HART TMT122】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。