DEMAG行车故障说明
查看问题
Crane: F001 1 CRD emergency stop relais PNOZ stationary tripped 检查地面站的安全继电器及急停(中仓的急停和地面站的急停)
Crane: F003 1 CRD main contactor crane is switch off 行车上的主接触器10d11-k025断开,检查急停按钮
Crane: F008 1 CRD emergency stop control pendant crane bridge pushed 检查行车的急停按钮
Crane: F009 1 CRD emergency stop relais PNOZ crane tripped 检查行车的安全继电器及急停按钮
Crane: F010 1 CRD emergency stop relais PNOZ crane tripped, from floor control 检查地面站的急停按钮或者大车和小车的急停
Crane: F012 1 CRD error synchronous run long travel 大车不同步,请检查大车的坐标,并调整大车主从单元的位置
Crane: F017 1 CRD limit switch long travel direction + tripped 检查大车的限位开关
Crane: F018 1 CRD limit switch long travel direction - tripped
检查大车的限位开关(中间的)
Crane: F020 1 CRD limit switch cross travel direction - tripped 检查小车的限位开关
Crane: F021 1 CRD emergency limit switch hoist unit direction + tripped
- 1 -
主钩的限位开关S1:
Crane: F023 1 CRD checking switch |hoist unit in transport height| is necessary 检查吸盘上顶锥的限位开关(中间继电器K067信号检查)
Crane: F024 1 CRD checking switch |no torsion of vacuum lifter| is necessary 检查行车上的防摇光电开关 I49.2
Crane: F025 1 CRD UPS: generator is running
检查发电机组
Crane: F027 1 CRD UPS: generator in manual mode
检查发电机组是否处于手动模式
Crane: F034 1 CRD SRP 2 : release signal from conveyor to crane has been taken back 检查 长泰系统中间继电器KC34 (检查地面站的卡件 E22.3信号是否
有)
Crane: F039 1 CRD error during checking SRP 2 occupied - empty 检查出库点的接近开关及光电开关
Crane: F059 1 CRD DP-slave control pendant KEBA (Crane) not running 检查操作手柄的电缆
Crane: F069 1 CRD DP-Slave distance laser long travel (master) failure 检查大车(主)的测距仪
Crane: F071 1 CRD DP-Slave distance laser cross travel failure 检查小车的测距仪
Crane: F080 1 CRD vacuum sensors at the kettle are indifferent
- 2 -
Crane: F087 1 CRD no sensor for roll diameter detection activated 检查吸盘上检测直径的接近开关
Crane: F088 1 CRD vacuum in kettle is below minimum value 检查真空泵电源或者管道漏气现象
Crane: F100 1 CRD mandrel not in normal working position (core to big-to-small)
检查纸卷的纸芯管是否有异物
Crane: F120 1 CRD motor circuit switch vacuum pump 1/4 (vacuum lifter) deenergised
吸盘上的真空泵没有电,检查真空泵的电源开关
Crane: F121 1 CRD overtemperature vacuum pump 1
真空泵电机过温
Crane: F125 1 CRD vaccum lifer .door cubicle is open 检查吸盘上配电柜的门
Crane: F126 1 CRD -- DW14.13(error signal test sensor transport position )
Crane: F127 1 CRD -- Communication to ground control interrupted 检查光通信仪或者地面站的开关电源有问题
Crane: F129 1 CRD error during checking position for pick Crane: F134 1 CRD weight of the roll out of the tolerance Crane: F136 1 CRD no heartbeat from SM in automatic mode
- 3 -
检查数据库中服务器(没有电)
Crane: F137 1 CRD error by emergency stop sensor lowering (mandrel) 检查导向锥的顶部光开
Crane: F138 1 CRD check correction senors mandrel, senors are not analysable 检查导向锥的光开
Crane: F139 1 Crd error during calculation |new set point |(emergency stop senor mandrel)
检查导向锥中间的光开
vacuum lifter not clearly free,Crane: F141 1 CRD -- DW16.12 (sensors of
check all sensors)
Crane: F142/3 1 CRD automatic mode: long travel axis (master/slave) out of destination area
大车没有走到位,检查行车的轨道
Crane: F161 1 CRD long travel(master) inverter not ready for start
Crane: F162 1 CRD long travel(master) fault inverter(过流)
Crane: F163 1 CRD long travel(master) motor circuit switch brake not OK Crane: F177 1 CRD long travel(master) error during brake lifting
Crane: F193 1 CRD long travel (slave) inverter not ready for start
Crane: F194 1 CRD long travel(slave) fault inverter(过流)
Crane: F195 1 CRD long travel (slave) motor circuit switch brake not OK
- 4 -
Crane: F209 1 CRD long travel (slave) error during brake lifting Crane: F215 1 CRD long travel (slave) switch off prelimit neg.direction not OK
检查大车的限位开关
Crane: F225 1 CRD cross travel inverter not ready for start Crane :F227 1 CRD cross travel motor circuit switch brake not OK Crane :F257 1 CRD hoist unit inverter not ready for start
Crane: F265 1 CRD hoist unit overload inverter
当断电时,会出现此现象,这是正常的工作状态,送电时,行车控制程序有自检测
时间,故会出现F265;过一段时间后自动消除。
Crane: F275 1 CRD hoist unit switch off prelimit pos.direction not OK
Crane: F276 1 CRD hoist unit switch off end limit pos.direction not OK Crane: F417 1 oil temperature vacuum pump 1 exceeds 60 Degree Celsius 1#真空泵油温超过60摄氏度
Crane: 1 CRD DP-Slave distance laser cross travel not running 检查小车的测距仪是否有电
Crane: Database-EXPORT-Error: Kopie auf Ersatz-LVR fehlgeschlagen -1 检查地面站的电源
Crane: Crane: Database-EXPORT-Error: EXPORT fehlgeschlagen -3 检查中仓的电脑或者服务器
- 5 -
硬件开关:上面是粗调:S4顺时针(临界点调S4来控制切掉高速,如果在高速运行时突然高速没有了,说明S4硬件限位没有调好重新调,向逆时调一点。调S4时,一定把S2的线接到S4上。)
下面是细调
介绍一下大车、小车、主钩 Reference points crane 介绍一下大车、小车、主钩 Reference points crane
long travel slave X2 : reference
positioning measuring long travel : 29 750 mm
system by laser
cross travel
positioning measuring system
Y : reference by distance laser
13 115 mm
cr
a
n
e
Y 1 Z long travel master X1 : reference
positioning measuring system long travel : 29 750 mm X by distance laser
Z : Preset Z : Preset crane : 18 160 mm use reference profile
Hoist with length of
positioning measuring system 1500 mm
by absolut encoder
- 6 -
本文档为【德马格行车故障含义说明】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。