Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KFD2-UT-Ex1Converters
Thermocouples
Signal processor
Cold junction
compensation
K-CJC
RTD
Sa
fe
a
re
a
H
az
ar
do
us
a
re
a
Output Power
supply
Power Rail
Input EEx ia IIC
7- 8+
RS 232
R
XD TX
D
G
ND
K-ADP1 PC
TTL
12- 11+
2-
2- 3+
2-1- 3+
2-1- 3+ 4+
21 3 4
1+
Composition
Current output 4 mA ... 20 mA
• 1-channel
• Input EEx ia IIC
• 24 V DC nominal supply voltage
• Accuracy ± 0.1 %
• Adjustment option of temperature
measuring range for Pt100, Ni100 in
2-, 3- or 4-wire versions
• Adjustment option of thermocouple
(B, E, J, K, L, N, R, S or T)
• Freely definable characteristic curve
for resistance 0 Ω ... 400 Ω and
voltage -50 mV ... 150 mV
• Internal/external cold junction
compensation
• Sensor burnout monitoring for
thermocouples
• Sensor burnout and short-circuit
monitoring (SC) for Pt100
• All settings via serial interface to PC
(online parameterisation)
• Prefabricated ex-works on request
• EMC acc. to NAMUR NE 21
The KFD2-UT-Ex1 is designed for the
connection of Pt100, Ni100 (2-, 3-, or 4-
wire version) and models B, E, J, K, L,
N, R, S, or T thermocouples. A current
signal of 4 mA ... 20 mA proportional to
the temperature is available at the
output.
The parameterisation occurs via
software in accordance with
VDI/VDE GMA 2187. The input is
galvanically isolated from the output,
the programming output and the power
supply. The PC's serial interface is
galvanically isolated from the
programming input by connecting the
K-ADP1 program adapter. The isolation
of the programming jack from the input
makes programming during operation
and through a connected measurement
circuit possible.
Internal or external cold junction
compensation may be selected by
using thermocouples.
The reaction to fault signals is
programmable (up or downscaled
output). A fault is indicated by a red
flashing LED per NAMUR NE 44.
Function
2
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Technical Data KFD2-UT-Ex1
11
28
79
_E
N
G
.x
m
l
20
03
-
05
-2
8
Supply
Connection Power Rail or terminals 11+, 12-
Rated voltage 20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1 W
Power consumption ≤ 1,5 W
Input
Connection terminals 1, 2, 3 and 4
suitable for Pt100, Ni100, Thermoelemente Typ B, E, J, K, L, N, R, S or T (IEC 584).
Configuration via programming socket.
Lead resistance ≤ 50 Ω per lead
Measuring current approx. 400 µA with resistance measuring sensor
current for lead breakage monitoring switched off during the measurement
Output
Connection terminals 7-, 8+
Current output 4 ... 20 mA ; 20,5 mA at input signal overrange ; fault signal: downscale 2 ... 4 mA or upscale 20.5 ... 22 mA
(programmable) ; load: ≤500 Ohm
Safety maximum voltage Um 250 V
Transfer characteristics
Deviation
After calibration Pt100: ± 0.01 % of measuring value in K + 0.05 % of span + 0.1 K (4-wire connection)
thermocouple: ± 0.05 % of measuring value in °C + 0.05 % of span + 1 K
This includes ± 0.8 K error of the cold junction compensation
Temperature current output (deviation of cjc included):
Pt100: (± 0.0015 % from measurement value in K + 0.006 % of range)/K ∆TU
*)
thermocouple: (± 0.02 K + 0.004 % from measurement value in °C + 0.006 % of range)/K ∆TU
*)
voltage output (deviation of cjc included):
Pt100: (± 0.0015 % from measurement value in K + 0.0075 % of range)/K ∆TU
*)
thermocouple: (± 0.02 K + 0.004 % from measurement value in °C + 0.0075 % of range)/K ∆TU
*)
*) ∆TU = ambient temperature change referenced to 23 °C (296 K)
Influence of supply voltage < 0.01 % of span
Influence of load ≤ 0,001 % of output value per 100 Ohm (current output)
Response time ≤ 430 ms
Electrical isolation
Input/Output safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Input/Power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Input/Programming input available
There is no electrical isolation between the programming input and the supply and output. The K-ADP1
interface (see section accessories and installation) provide galvanic isolation so that ground loops are
avoided.
Standard conformity
Coordination of insulation acc. to DIN EN 50178
Electrical isolation acc. to DIN EN 50178
Electromagnetic compatibility acc. to EN 50081-2 / EN 50082-2, NAMUR NE 21
Climatic conditions acc. to DIN IEC 721
Directive conformity
Electromagnetic compatibility standards
Directive 89/336/EG on request
Ambient conditions
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Mechanical specifications
Protection degree IP20
Mass approx. 110 g
Data for application in conjunction
with hazardous areas
EC-Type Examination Certificate BAS 01 ATEX 7256 ; for additional certificates refer to the approval list
Group, category, type of protection ¬ II (1) G D [EEx ia] IIC (-20 °C ≤ Ta ≤ 60 °C)
Voltage U0 11 V
Current I0 33 mA
Power P0 90 mW
Supply
Safety maximum voltage Um 250 V
Type of protection [EEx ia]
Explosion group IIA IIB IIC
External capacitance 60 µF 13,8 µF 1,97 µF
External inductance 251 mH 121 mH 32 mH
Internal capacitance (EEx ia) 0 µF
3
11
28
79
_E
N
G
.x
m
l
20
03
-
05
-2
8
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KFD2-UT-Ex1
Internal inductance (EEx ia) 0 mH
Statement of conformity TÜV 02 ATEX 1797 X (observe statement of conformity)
Group, category, type of protection,
Temperature classification
¬ II 3 G EEx nA II T4
Electrical isolation
Input/Output safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Input/Power supply safe electrical isolation acc. to EN 50020, voltage peak value 375 V
Directive conformity standards
Directive 94/9 EU on request
Entity parameter
Certification number 4Z6A5.AX
FM control drawing No. 116-0129
Suitable for installation in division 2 yes
Connection terminals 1, 2, 3, 4
Input I
Voltage VOC 11,6 V
Current It 30,9 mA
Explosion group A&B C&E D, F&G
Max. external capacitance Ca 1,83 µF 5,48 µF 14,61 µF
Max. external inductance La 35,9 mH 128,2 mH 307,1 mH
Safety parameter
CSA control drawing LR 65756-13
Control drawing No. 116-0132
Connection terminals 1, 2, 3, 4, 5
Input I
Voltage VOC 10,5 V
Explosion group A&B C&E D, F&G
Max. external capacitance Ca 2,6 µF 8 µF 21 µF
Max. external inductance La 45 mH 160 mH 387 mH
PR-03 Power Rail
UPR-03 Power Rail
KFD2-EB2 power feed module
The devices are supplied with 24 VDC through the KFD2-EB2 power feed module and the PR-03 or the UPR-03 Power Rail.
Each power feed module monitors and provides protection for groups of as many as 100 individual devices. The PR-03 Power
Rail is an insert component for the DIN rail. The UPR-03 Power Rail is a complete unit consisting of an electrical insert and an
aluminium DIN rail measuring 35 mm x 15 mm x 2000 mm. The devices are simply snapped in place to make electrical
contact.
If a Power Rail is not being used, power can be supplied to the devices directly through the device terminals.
K-CJC
Removable terminals with integrated temperature measurement sensor for cold junction compensation for thermocouples.
PACTware™
Device-specific drivers (DTM)
Adapter K-ADP1
Interface adapter for connection with the serial interface of a PC/Notebook.
Accessories