Installation and start up instructions
Overload relay type RMP-111D
uni-line
4189340123E (UK)
• Protection of prime mover
• 3 phase measurement
• LED indication of fault condition
• Timer controlled tripping
• LED indication for activated relay
• 35 mm DIN rail or base mounting
Page 2 of 4 Tel. (+45) 9614 9614 • Fax: (+45) 9614 9615 • E-mail: deif@deif.com
Mounted voltage module
Contact remains locked
in alarm position even though
the input returns to normal.
Latch circuit is reset by
disconnecting the supply voltage.
Distributors ID No.
Filled in by distributor
when customizing the unit.
Measuring voltage
Coupling
(set by DEIF)
Supply voltage
Type designation DEIFs order ack. No.
To be stated when contacting DEIF
Highest voltage
in relation to earth
Installation category
Special calibration
(if non-standard calibration is applied)
Scaling 1
(for adaption of the unit
to the measuring power)
Calibrated secondary
power of the relay
Mounted standard current module
Relay coupling
Shown is relay B as a
normally de-energised
relay, relay C as a
normally energised relay
with latch circuit
1. Description
This protective overload relay type RMP-111D forms part of a complete DEIF series
(the uni-line) of relays for protection and control of generators.
2. Label
The relay is provided with a label with the following data:
Note 1: Calculation of measuring power:
X x voltage module x current module x scale = measuring power
X is replaced by 2 for coupling 2W3
3 for couplings 1W3, 1W4, 3W3 and 3W4
Note: The relay is provided with a 200 ms power-up relay, ensuring correct
function of the relay on connection of the auxiliary voltage.
Normally energised contacts (NE) are not activated (contact does not
open/close) until 200 ms after connection of the auxiliary voltage.
Likewise, the relay is provided with a 200 ms power-down circuit, ensuring
supervision and maintenance of any set point exceeding for 200 ms after
disconnection of the auxiliary voltage.
Installation and start up instructions RMP-111D
4189340123E (UK)
3. Mounting instructions
The RMP-111D is designed
for panel mounting, being
mounted on a 35 mm DIN rail,
or by means of two 4-mm
screws.
Weight: Approx. 0.650 kg
The design of the relay makes mounting of it close to other uni-line units possible,
however make sure there are min. 50 mm between the top and bottom of this relay and
other relays/units.
The DIN rail must always be placed horizontally when several relays are mounted on
the same rail.
4. Connection diagram
2W3 3W3(4)
A 2A fuse may protect all voltage inputs.
The relay is protected against ESD (electrostatic electricity), and further special
protection against this during the mounting of the relay is not necessary.
Coupling Applied for measurement on
3W3 3 phase networks without neutral
3W4 3 phase networks with neutral
If neutral is not accessible, the connection to terminal No. 16 (neutral) may
be omitted without this affecting the accuracy of the relay, provided that
the 3 phase voltages are identical.
Page 4 of 4 Tel. (+45) 9614 9614 • Fax: (+45) 9614 9615 • E-mail: deif@deif.com
For relays with coupling 2W3 the voltage inputs are connected as follows, if the current
transformers are placed in other phases than indicated in the above diagram:
External current transformer Connect
- connected to L1 (23 + 24),
and to L2 (29 + 30)
L1
to term. No. 17
L3
to term. No. 19
L2
to term. No. 21
- connected to L2 (23 + 24),
and to L3 (39 + 30)
L2
to term. No. 17
L1
to term. No. 19
L3
to term. No. 21
5. Start up instructions
5.1 Setting and indication
Setting of LED/relay
Overload set point:
(25
125%) of Pn
P> Yellow LED is lit when the set point has been
exceeded, but the output contact has not yet been
activated.
Time delay:
0
20 s
The contact is activated and the red LED is lit after the timer
has expired.
When setting the set points on the front of the RMP-111D an accuracy of ±5% of the
scaling may normally be obtained.
If a higher accuracy is required, the unit (the generator) connected to the relay must be
loaded by means of a load bank. When the power exceeds the set point, the yellow
LED of the RMP-111D is lit.
6. Technical specifications
Overload, currents: 4 x In, continuously
20 x In for 10 s (max. 75A)
80 x In for 1 s (max. 300A)
Load: Max. 0.5VA per phase
Overload, voltages: 1.2 x Un, continuously
2 x Un for 10 s
Load: 2kΩ/V
Frequency range: 40
45
65
70Hz
Relay contact: 1 changeover switch
Contact ratings: 250V-8A-2000A (AC), 24V-8A-200W (DC)
Contact voltage: Max. 250V (AC). Max 150V (DC)
Response time: <400 ms
Galv. separation: Between inputs, outputs and aux. supply: 3250V-50Hz-1 min.
Consumption: (Aux. supply) 3.5VA/2W